Document Citation: 40 TAC § 19.330

Header:
TEXAS ADMINISTRATIVE CODE
TITLE 40. SOCIAL SERVICES AND ASSISTANCE
PART 1. DEPARTMENT OF AGING AND DISABILITY SERVICES
CHAPTER 19. NURSING FACILITY REQUIREMENTS FOR LICENSURE AND MEDICAID CERTIFICATION
SUBCHAPTER D. FACILITY CONSTRUCTION



Date:
08/31/2009

Document:
40 TAC § 19.330 (2011)

§ 19.330. Construction and Initial Survey of Completed Construction

(a) Construction phase.

(1) DADS Regulatory Services Division in Austin, Texas, must be notified in writing of construction start.

(2) All construction must be done in accordance with minimum licensing requirements. It is the sponsor's responsibility to employ qualified personnel to prepare the contract documents for construction of a new facility or remodeling of an existing facility. Contract documents for additions and remodeling and for the construction of an entirely new facility must be prepared by an architect licensed by the Texas State Board of Architectural Examiners. Drawings must bear the seal of the architect. Certain parts of contract documents (including final plans, designs, and specifications) must bear the seal of a licensed professional engineer approved by the Texas Board of Professional Engineers to operate in Texas or, as permitted by subsections (b)(12) and (15) of this section, signed by a Responsible Managing Employee or Alarm Planning Superintendent licensed by the State Fire Marshal's Office. These certain parts include sheets and sections covering structural, electrical, mechanical, sanitary, and civil engineering.

(A) Remodeling is the construction, removal, or relocation of walls and partitions, the construction of foundations, floors, or ceiling-roof assemblies, the expanding or altering of safety systems (including, but not limited to, sprinkler, fire alarm, and emergency systems), or the conversion of space in a facility to a different use.

(B) General maintenance and repairs of existing material and equipment, repainting, applications of new floor, wall, or ceiling finishes, or similar projects are not included as remodeling, unless as a part of new construction. DADS must be provided flame spread documentation for new materials applied as finishes.

(b) Contract documents.

(1) Site plan documents must include grade contours; streets (with names); north arrow; fire hydrants; fire lanes; utilities, public or private; fences; unusual site conditions, such as ditches, low water levels, other buildings on-site; and indications of buildings five feet or less beyond site property lines. Site plan documents for nursing facilities may include the developed landscaping plan for resident use as called for in § 19.332(f) of this chapter (relating to Location and Site).

(2) Foundation plan documents must include general foundation design and details.

(3) Floor plan documents must include room names, numbers, and usages; resident care areas; doors (numbered) including swing; windows; legend or clarification of wall types; dimensions; fixed equipment; plumbing fixtures; and kitchen basic layout; and identification of all smoke barrier walls (outside wall to outside wall) or fire walls.

(4) For both new construction and additions or remodeling to existing buildings, an overall plan of the entire building must be drawn or reduced to fit on an 8 1/2 inch by 11 inch sheet.

(5) Schedules must include door materials, widths, types; window materials, sizes, types; room finishes; and special hardware.

(6) Elevations and roof plan must include, but is not limited to, exterior elevations, including material note indications and any roof top equipment, roof slopes, drains, and gas piping, and interior elevations where needed for special conditions.

(7) Details must include wall sections as needed (especially for special conditions); cabinet and built-in work, basic design only; cross sections through buildings as needed; and miscellaneous details and enlargements as needed.

(8) Building structure documents must include structural framing layout and details (primarily for column, beam, joist, and structural frame building); roof framing layout (when this cannot be adequately shown on cross section); cross sections in quantity and detail to show sufficient structural design and structural details as necessary to assure adequate structural design, also calculated design loads.

(9) Electrical documents must include electrical layout, including lights, convenience outlets, equipment outlets, switches, and other electrical outlets and devices; service, circuiting, distribution, and panel diagrams; exit light system (exit signs and emergency egress lighting); emergency electrical provisions (such as generators and panels); and similar systems (such as control panel, devices, and alarms); a nurse call system; and sizes and details sufficient to assure safe and properly operating systems.

(10) Plumbing documents must include plumbing layout with pipe sizes and details sufficient to assure safe and properly operating systems, water systems, sanitary systems, gas systems, other systems normally considered under the scope of plumbing, fixtures, and provisions for combustion air supply.

(11) Heating, ventilation, and air-conditioning (HVAC) documents must include sufficient details of HVAC systems and components to assure a safe and properly operating installation including, but not limited to, heating, ventilating, and air-conditioning layout, ducts, protection of duct inlets and outlets, combustion air, piping, exhausts, and duct smoke and/or fire dampers; and equipment types, sizes, and locations.

(12) Fire sprinkler system plans and hydraulic calculations, must be designed in accordance with the applicable sections of the National Fire Protection Association (NFPA) 13, and signed by a Responsible Managing Employee, licensed by the State Fire Marshal's Office, or sealed by a licensed professional engineer.

(13) Other layouts, plans, or details as may be necessary for a clear understanding of the design and scope of the project; including plans covering private water or sewer systems must be reviewed by the local health or wastewater authority having jurisdiction.

(14) Specifications must include installation techniques, quality standards and/or manufacturers, references to specific codes and standards, design criteria, special equipment, hardware, painting, and any others as needed to amplify drawings and notes.

(15) Fire detection and alarm system working plans must be designed in accordance with the applicable sections of the National Fire Alarm and Signaling Code, NFPA 72, and the National Electric Code, NFPA 70, and signed by an Alarm Planning Superintendent licensed by the State Fire Marshal's Office or sealed by a licensed professional engineer.

(c) Initial survey of completed construction.

(1) Upon completion of construction, including grounds and basic equipment and furnishings, a final construction inspection (initial survey) of the facility, including additions or remodeled areas, is required to be performed by DADS' architectural inspecting surveyor prior to occupancy. The completed construction must have the written approval of the local authorities having jurisdiction, including the fire marshal and building inspector.

(2) The inspection described in paragraph (1) may be obtained on an expedited basis. An applicant may obtain a Life Safety Code inspection within 15 business days after DADS receives a written request if the applicant submits:

(A) a complete application as required in § 19.201(b) of this chapter (relating to Criteria for Licensing) and § 19.204 of this chapter (relating to Application Requirements); and

(B) the appropriate Life Safety Code fee listed in § 19.220 of this chapter (relating to Expedited Life Safety Code and Physical Plant Inspection Fees).

(3) After the completed construction has been surveyed by a representative of DADS' architectural section and found acceptable, this information will be conveyed to the licensing officer as part of the information needed to issue a license to the facility. In the case of additions or remodeling of existing facilities, a revision or modification to an existing license may be necessary. Note that the building, grades, drives, parking, and grounds must be essentially 100% complete at the time of this initial survey visit for occupancy approval and licensing, including basic furnishings and operational needs.

(4) A copy of the following documents must be provided to DADS' architectural inspecting surveyor at the time of the survey of the completed building:

(A) written approval of local authorities as called for in paragraph (1) of this subsection;

(B) record drawings of the fire detection and alarm system as installed, signed by an Alarm Planning Superintendent licensed by the State Fire Marshal's Office or sealed by a licensed professional engineer, including a sequence of operation, the owner's manuals and the manufacturer's published instructions covering all system equipment, a signed copy of the State Fire Marshal's Office Fire Alarm Installation Certificate, and, for software-based systems, a record copy of the site-specific software (excluding the system executive software or external programmer software) in a non-volatile, non-erasable, non-rewritable memory;

(C) documentation of materials used in the building which are required to have a specific limited fire or flame spread rating including, but not limited to, special wall finishes or floor coverings, flame retardant curtains (including cubicle curtains), and rated ceilings. This must include a signed letter from the installer verifying that the material installed, such as carpeting, is the same material named in the laboratory test document;

(D) record drawings of the fire sprinkler system as installed, signed by a Responsible Managing Employee licensed by the State Fire Marshal's Office or sealed by a licensed professional engineer, including the hydraulic calculations, alarm configuration, aboveground and underground Contractor's Material and Test Certificate, all literature and instructions provided by the manufacturer describing the proper operation and maintenance of all equipment and devices in accordance with Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, NFPA 25;

(E) service contracts for maintenance and testing of systems, including, but not limited to, alarm systems and sprinkler systems;

(F) a copy of gas test results of the facility's gas lines from the meter;

(G) a written statement from an architect and/or engineer stating that he certifies that the building was constructed to meet NFPA 101, Life Safety Code, and all locally applicable codes, and that the facility is in substantial conformance with minimum licensing requirements; and

(H) the contract documents specified in subsection (b) of this section.

(d) Nonapproval of new construction.

(1) If, during the survey of completed construction, the surveyor finds certain basic requirements not met, DADS will not license the facility or approve it for occupancy. Such basic items may include the following:

(A) construction which does not meet minimum code or licensure standards for basic requirements such as corridor widths being less than eight feet clear width, ceilings installed at less than the minimum seven feet six inches height, resident bedroom dimensions less than required width, and other similar features which would disrupt or otherwise adversely affect the residents and staff if corrected after occupancy;

(B) no written approval by local authorities;

(C) fire protection systems not completely installed or not functioning properly including, but not limited to, fire alarm systems, emergency power and lighting, and sprinkler systems;

(D) required exits are not all usable according to Life Safety Code requirements;

(E) telephone not installed or not properly working;

(F) sufficient basic furnishings, essential appliances and equipment are not installed or not functioning; and

(G) any other basic operational or safety feature which the surveyor, as the authority having jurisdiction, encounters which in his judgment would preclude safe and normal occupancy by residents on that day.

(2) If the surveyor encounters deficiencies that do not affect the health and safety of the residents, licensure may be recommended based on an approved written plan of correction by the facility's administrator.

(3) Copies of reduced size floor plan on an 8 1/2 inch by 11 inch sheet must be submitted in duplicate to DADS for record and/or file use and for the facility to use in evacuation planning and fire alarm zone identification. The plan must contain basic legible information such as overall dimensions, room usage names, actual bedroom numbers, doors, windows, and any other pertinent information.